Analysis on 60EL-2 Action Due to the Action of F5 Arrester of Pole Ⅰ Low-end Valve Hall in Yun-Guang UHVDC Project
The ±800 kV Chu-Sui UHVDC project is the first ±800 kV UHVDC transmission engineering in the world. Its transmission capacity is bipolar 5 000 MW. This project adopts dual twelve pulse valve groups in series
and each pole includes a high-end valve group and a low-end valve group. In the island debugging test of Chuxiong DC converter station on 15 December
2012
the action of F5 arrester of low-end valve hall led to the actions of the pole’s differential protection DC DIFF 87DCM-ESOF
the valve group’s short circuit protection short circuit 87 CSD stage1
and the current unbalance protection electrode line 60EL-2 monopolar
and made the pole I two valve groups locked. The action of valve hall arrester was very rare in the past HVDC projects
and usually resulted in DC protections. In this paper
the reason why the action of valve hall F5 arrester leads to the action of current unbalance protection 60EL-2 of grounding pole line is analyzed
and some suggestions are provided for the insulation design of grounding pole line of HVDC project.