QIU Taihong, LI Guowei, LUO Rongbo, et al. Application of On-line Detection Technology in the Fault Diagnosis of Transformer Bushing[J]. High voltageapparatus, 2015, 51(9): 159-163.
QIU Taihong, LI Guowei, LUO Rongbo, et al. Application of On-line Detection Technology in the Fault Diagnosis of Transformer Bushing[J]. High voltageapparatus, 2015, 51(9): 159-163. DOI: 10.13296/j.1001-1609.hva.2015.09.027.
Application of On-line Detection Technology in the Fault Diagnosis of Transformer Bushing
Aiming at the phenomena that the dielectric loss and capacitance exceeded the specified values in conventional test of high-voltage C-phase bushing of the No. 2 transformer in the 110 kV substation
Foshan Power Supply Bureau
and acetylene was also found in the oil test
on-line detection was conducted for the bushing and the existence of a defect was determined. Hence
high-voltage dielectric loss and partial discharge tests
as well as disassembly inspection
were performed to find the traces of discharge on the first and second screens of the bushing
which verified the result of the on-line detection.