Case Study on Abnormal Dielectric Loss of a ±800 kV DC Wall Bushing with Countermeasures
The abnormal phenomena of dielectric loss and gas components of a DC wall bushing in a±800 kV converter station was analyzed. Several high-voltage tests and gas components analysis on the UHVDC wall bushing were conducted on site
and the bushing was disassembled and tested in the manufacturer. The results show that: 1)The discharge point is at the connection of the compressive ring and the metal guide bar of outdoor bushing; 2)Many white conductive powder mainly composed of Al F3 are found in the bushing; and 3)This conductive powder is the main cause of abnormal dielectric loss of the wall bushing. Some methods are presented for repairing the outdoor bushing
and suggestions are made for manufacture supervision