YANG Bo, WANG Deshun, ZHAO Shanglin, et al. Insulation Coordination Optimization Design for Low Voltage Ride Through Test Device of 35 kV Grid-connected Photovoltaic System[J]. High voltageapparatus, 2015, 51(10): 8-12.
YANG Bo, WANG Deshun, ZHAO Shanglin, et al. Insulation Coordination Optimization Design for Low Voltage Ride Through Test Device of 35 kV Grid-connected Photovoltaic System[J]. High voltageapparatus, 2015, 51(10): 8-12. DOI: 10.13296/j.1001-1609.hva.2015.10.002.
Insulation Coordination Optimization Design for Low Voltage Ride Through Test Device of 35 kV Grid-connected Photovoltaic System
In order to avoid insulation breakdown failure of reactor tap to the surrounding zero potential or between tap in process of 35 kV grid-connected photovoltaic system operation in high altitude environmen
in this paper
combining with operating overvoltage measurement test in process of the production design
the electric distribu-tion in the condition of high amplitude operating overvoltage by finite element method
the insulation weak area in the device is analyzed and the present optimization suggestions are presented. The conclusion is: adding insulation board between wire tap
increasing the surface area of nut
improving curvature of wire tap and the electric clearance can make the electric field which is distorted more even