BIE Rui, QIU Huimin, WU Bo, et al. Overvoltage Level Research in Zhaotong Converter Station with Xiluodu Right Side HVDC Project in Islanded Operation Mode[J]. High voltageapparatus, 2015, 51(10): 54-62.
BIE Rui, QIU Huimin, WU Bo, et al. Overvoltage Level Research in Zhaotong Converter Station with Xiluodu Right Side HVDC Project in Islanded Operation Mode[J]. High voltageapparatus, 2015, 51(10): 54-62. DOI: 10.13296/j.1001-1609.hva.2015.10.009.
Overvoltage Level Research in Zhaotong Converter Station with Xiluodu Right Side HVDC Project in Islanded Operation Mode
With double-circuit bipolar trip of Xiluodu-Guangdong HVDC project in islanded mode
the overvoltage will occur to Zhaotong converter station as the sending power grid. Its overvoltage level and the corresponding conditions of the AC filter and arrester will determine the safety and stability of islanding operation. Thus
with considering of practice connection mode
the different island operation modes and filter configuration are analyzed.The AC side overvoltage level and arrester working conditions of Zhaotong converter station are studied in case of double-circuit bipolar simultaneous trip(ESOF or BLOCK)
double-circuit bipolar successive trip and AC system faults in sending and receiving power grid by using PSCAD/EMTDC. For taking measures of cutting AC filter bank or group and considering the case of a group cutting half-cycle before the other
the effects of transient recovery voltage and capacitive breaking current of the AC filter breaker on the islanded operation mode are studied. Through the system simulation and comprehensive analysis above
it is of a certain engineering significance for providing the technical basis for the actual operation of the DC system site and dealing with islanded operation failure.