Study on Surface Discharge Characteristics of Insulator in SF6 Under Oscillating Impulse Voltage
The on-site oscillating impulse withstand voltage(OIV)test for high-voltage level of GIS has been widely carried out in recent years. In order to make this OIV test develop into a comprehensive diagnostic test
an oscillatory impulse voltage generator was designed and built to produce the voltage waveforms in accordance with the IEC 60060-3—2006 standard
and the partial discharge(PD)measurement system was also developed. Then PD characteristics of insulator in SF6 under OIV were studied in this paper. The features of typical discharge pulses were summarized; the variation of discharge amplitude maximum and discharge number with the increase of applied voltage was also analyzed. Moreover
the process of discharge was discussed. The results showed that the number of surface discharge pulses increased dramatically due to oscillatory property
and so that it is better to detect hidden flaws in GIS; the maximum discharge amplitude and discharge number also increased significantly with the increase of applied voltage. This study provided a basis for PD detection in OIV test.