Development of an Assembly Joint for Calibration on SF6 Gas Density Monitor
This paper expounds the necessity of calibration on SF6 gas density monitor and analyzed the problems existing in the field. In order to solve the problem of false operation that could happen during the calibration on site
we put forward and developed the SF6 gas density monitor calibration with joint assembly. With the joint assembly
in the same port one can refill and measure the moisture
or automatically shut off the SF6 gas link and calibrate the SF6 density monitor. The power maintenance personnel need not to remove density monitor and SF6 gas density monitor can be calibrated. False operations can also be completely prevented. Great convenience can be brought to the maintenance personnel and greatly improve the work efficiency and the accuracy of the job
thus ensuring the healthy running of power supply equipment.