Distribution Characteristics of the Contamination Along the Insulator String in ±500 kV DC Transmission Line
aimed at the representative and typical insulator strings for Xing’an ± 500 kV DC transmission line
sampling plan of artificial contamination is developed
field sampling is carried out
and the treatment of contaminated samples is analyzed. And in-depth analysis of the contamination characteristics along the string of different materials and different shapes insulator string type of insulator strings. Studies show that the contamination of the insulator string in high voltage direct current transmission line is affected by both natural pollution and electric field
salt density of the high voltage side is greater than that of the low voltage side; Salt density on the upper surface is not necessarily less than the lower surface; in the form of different styles of sheds
the small insulator sheds have the greatest contamination degree; rational design shed profile structure has an important role to improve stain resistance. The research provide guidance for the power sector to optimize the external insulation of overhead transmission line configuration
and to develop the operation and maintenance strategy.