FANG Shuai, YUAN Zhao, YU Xinlin, et al. Topology Optimization of HVDC Circuit Breaker with Forced Current Zero[J]. High voltageapparatus, 2015, 51(11): 53-58.
FANG Shuai, YUAN Zhao, YU Xinlin, et al. Topology Optimization of HVDC Circuit Breaker with Forced Current Zero[J]. High voltageapparatus, 2015, 51(11): 53-58. DOI: 10.13296/j.1001-1609.hva.2015.11.009.
Topology Optimization of HVDC Circuit Breaker with Forced Current Zero
As the main research direction of mechanical HVDC circuit breaker
forced current zero is of simple mature technology and high operating reliability. Based on the actual DC grid
the simulation analysis on the short circuit at the rectifier outlet of DC line
may be the most serious malfunction to DC circuit breaker
has been conducted. On the basis of this analysis
the two flaws of current topology are found and two topology optimization strategies are proposed
including installing surge arrester in parallel with the commutation capacitance and installing energy absorption components in parallel with the smoothing reactor
which can effectively reduce peak voltage between commutation capacitance and peak voltage between the mechanical switch.