QIN Taotao, HUANG Zhihui, DONG Enyuan, et al. Investigations on the Appearance Evolution of Vacuum Arcs in the DC Interruption[J]. High voltageapparatus, 2015, 51(11): 59-63.
QIN Taotao, HUANG Zhihui, DONG Enyuan, et al. Investigations on the Appearance Evolution of Vacuum Arcs in the DC Interruption[J]. High voltageapparatus, 2015, 51(11): 59-63. DOI: 10.13296/j.1001-1609.hva.2015.11.010.
Investigations on the Appearance Evolution of Vacuum Arcs in the DC Interruption
and the method of forced current zero is used to interrupt DC current in synthetic test circuit. Under different frequencies of commutation current
different arcing time and different pre-charged voltages
the process of arc burning and arc appearance is observed by a high speed CMOS camera. Analysis is conducted according to the arc area obtained by the image processing technology.Experimental results show that interrupting the DC current with low frequency commutation current benefits for the recovery of dielectric strength. Different pre-charged voltages have nearly no influence on the arc appearance. The more metal vapor will be produced when the arcing time is longer