WEI Peng, LIU Jiankun, ZHOU Qian, et al. Modeling and Simulation of UHVDC Transmission System from Jinping to Sunan Based on the RTDS Simulation Platform of UHVDC Control and Protection[J]. High voltageapparatus, 2015, 51(11): 134-139.
WEI Peng, LIU Jiankun, ZHOU Qian, et al. Modeling and Simulation of UHVDC Transmission System from Jinping to Sunan Based on the RTDS Simulation Platform of UHVDC Control and Protection[J]. High voltageapparatus, 2015, 51(11): 134-139. DOI: 10.13296/j.1001-1609.hva.2015.11.022.
Modeling and Simulation of UHVDC Transmission System from Jinping to Sunan Based on the RTDS Simulation Platform of UHVDC Control and Protection
Traditional study on integration of Jiangsu power grid with DC transmission from Jinping to Sunan(JinSu)only stays in pure digital electromechanical-electromagnetic hybrid simulation. With the development of simulation technology it can’t meet the analysis needs. Refer to the Jin-Su project the primary system of Jin-Su project is built on real-time digital simulation device(RTDS). Secondary control and protection simulation systems are built by actual control and protection device to form a closed loop simulation platform with RTDS. Its performance remain highly consistent with actual UHVDC project in protection functions
behavior and trends of steady-state operating conditions
under fault of AC and DC and other aspects of characteristics. Operating characteristics ACDC hybrid power grid are studied. Taking a real commutation failure caused by AC fault as background the simulation results of the platform and traditionally ADPSS based electromechanical-electromagnetic hybrid simulation results are compared with the real fault recorder. The accuracy and availability of the platform are verified.