Analysis of an Abnormal GRTS Transfer in DC Double Circuit Transmission System
This article involves the first DC double circuit transmission project in China. The double parallel lines on the same tower have caused the rise of the transmission line induced voltage. It has affected the neutral zone equipment in the DC field of the convertor station and has no experience reference. The article describes an abnormal GRTS transfer accident
and researches its cause and potential danger. According to the result
the article proposes some anti-accident measures and suggestions. The conclusion is useful both for the design of the equipments’ insulation level and operational maintenance work.