Calculation and Analysis on Surface Electric Field Intensity of Bundled Conductors for UHVAC Transmission Lines
According to the actual situation of the UHVAC transmission lines
the surface electric field intensity on the bundled conductors is calculated based on the dipole method. Then
the effects of the factors
such as the average height of lines to ground
layout
bundled distance
distance among phases
number of bundles
cross-section area of a conductor
phase sequence
and shielding lines
on the surface electric field intensity of bundled conductors are analyzed and discussed. The results show that: 1 The surface electric field intensity of the bundled conductors is different; 2 The number of bundles and cross-section area of a conductor impose significant effects on the surface electric field intensity
while other factors
such as the average height of lines to ground
layout
bundled distance
and distance among phases
impose relatively smaller effects on the surface electric field intensity; 3 The phase sequence has significant effect on the surface electric field intensity of the top and bottom phases of transmission lines
and has smaller effect on the middle phase; and 4 The shielding lines can enhance the surface electric field intensity of bundled conductors.