ZHENG Zhong, FENG Wei, PAN Chunhui, et al. Detection and Electric Field Analysis of Surface Defects on Porcelain Post Insulator[J]. High voltageapparatus, 2015, 51(12): 38-42.
ZHENG Zhong, FENG Wei, PAN Chunhui, et al. Detection and Electric Field Analysis of Surface Defects on Porcelain Post Insulator[J]. High voltageapparatus, 2015, 51(12): 38-42. DOI: 10.13296/j.1001-1609.hva.2015.12.007.
Detection and Electric Field Analysis of Surface Defects on Porcelain Post Insulator
The power grid has bad experiences with high voltage post insulator breakdown
which cause further power outage and equipment damage. The failure statistics shows the failure patterns and indicates the most vulnerable position along the pole. The precursory scenario of such breakdown
where a small groove appears at the bottom surface of the pole
is analyzed for the spatial electric field distribution using finite element method. The analyses show large electric field variation at the point of defect
which gives rise to an innovative approach to detect such defect prior to failures. The feasibility and sensitivity of such method is discussed and the online field interferences are cleaned.