Simulation of Ferroresonance Overvoltage Caused By Commissioning 500 kV Auto-transformer Based on the PSCAD
the ferroresonance overvoltage caused by commissioning 500 kV auto-transformer gradually reduced. But in the thinner terminal station of the power grid structure
due to the improper way of debugging
the main transformer was still likely to inspire ferroresonance. To solve the above problems
the author take the terminal 500 kV Han-Ta stations of North China power grid as an example
on the research of the auto-transformer ferroresonance excitation characteristics
developed the BPA-PSCAD equivalent interface program
it modeled and calculated the possible ferroresonance overvoltage
natural resonant frequency
operating overvoltage and excitation inrush current in the starting mode of the long line and commissioning main transformer with no-load
to avoid the resonance failure occurs
it puts forward the right way to start debugging
the studyings for the debugging plans provides the feasible theory basis
it is significance for the terminal station of the main transformer to cut and run.