Fault Analysis and Treatment of a 500 kV SF6 Porcelain Column Circuit Breaker
An opening fault of a 500 kV SF6 porcelain column circuit breaker is analyzed. The defect in circuit breaker is located by X-ray digital radiography(XDR). Disassembly inspection of arc quenching chamber reveals that the fault is directly due to fracture of the horizontal drive shaft that drives the breaker contacts. Subsequently
this arc quenching chamber of the faulty equipment is replaced. And chemical
mechanical and electrical tests are conducted for the driving rod’s assembly parts in terms of material
part size and non-conventional force to eventually find the ultimate causes of the fault. In addition