JIN Yinxie, CUI Xiang, WU Hengtian. Compensation Capacitor for Curved Part of GIS[J]. High voltageapparatus, 2016, 52(1): 79-85. DOI: 10.13296/j.1001-1609.hva.2016.01.014.
来表示电磁波在L型GIS结构处的畸变影响。通过对1 000 k V及500 k V含有L型拐弯段的GIS管道计算
获得了两种电压等级情况下GIS拐弯段的最佳补偿电容值分别5 p F与7.5 p F。
Abstract
In gas-insulated substation(GIS)
very fast transient overvoltage(VFTO)generated by the switching operation has a great impact on the insulation structures in GIS. In order to study the VFTO waveform and calculate the magnitude of VFTO
an accurate GIS pipe model is necessary. In this paper
both the transmission line method and the full-wave electromagnetic field method(finite-difference time-domain(FDTD)method)are used to establish a model of L-type GIS
respectively. The transmission line method and the FDTD method are employed to calculate the full waveform of VFTO
while their results are quite different. To modify the transmission line method
a compensation capacitor is added to the L-type section of GIS in the transmission line model to reveal the distortion of electromagnetic wave at the section. Calculations of the L-type section of GIS pipe under the voltages of 1 000 k V and 500 k V show that the optimum capacitance of the compensation capacitor is 5 p F and 7.5 p F