Distinction Between Non-sustained Disruptive Discharge(NSDD)and Restrike in Capacitive Current Switching Test
Non-sustained disruptive discharge(NSDD)is a voltage breakdown after the vacuum circuit-breaker open the fault current which will not cause the recovery of power frequency current. Restrike is different from NSDD
the recovery of power frequency current between the contacts will make the breaker failed. It’s not easy to show the distinction between NSDD and restrike during some type tests. Clear appraisal procedure isn’t given in the relevant standard. By calculating the process of break-down in single phase capacitive circuit and substitute circuit for non-effectively earthed systems during three-phase capacitive current switching test
and analyzing the character of the vacuum circuit-breaker during the capacitive current breaking
finally
this paper shows the distinction and give an example between NSDD and restrike in effectively earthed neutral systems and also in noneffectively earthed systems for three-phase capacitive current switching test. By analyzing the viewpoint developing about NSDD in both domestic and foreign standard
this paper gives the clear explanation about NSDD in the guide
It’s an important supplement for the national standard and STL guide.