LYU Fangcheng, HAN Fang, WANG Fochi, et al. Overvoltage in CRH Reactor Lifting Process and Simulation Analysis of Restraining Measures[J]. High voltageapparatus, 2016, 52(2): 1-6+12.
LYU Fangcheng, HAN Fang, WANG Fochi, et al. Overvoltage in CRH Reactor Lifting Process and Simulation Analysis of Restraining Measures[J]. High voltageapparatus, 2016, 52(2): 1-6+12. DOI: 10.13296/j.1001-1609.hva.2016.02.001.
Overvoltage in CRH Reactor Lifting Process and Simulation Analysis of Restraining Measures
China Railway High-speed(CRH)train will produce overvoltage problem during passing neutral section
lifting reactor and so on. Aiming at this phenomenon of overvoltage
this paper builds reactor lift equivalent circuit by using the simulation software MATLAB
establishing simulation model of potential transformer installed on the roof. Combining simulation and theory
it is pointed that low-voltage transformer ferromagnetic oscillations in the reactor drop process will result in overvoltage. In the reactor raise process
overvoltage is superimposed on the steady-state component of the supply voltage and transient component of high frequency oscillation circuit itself. Comparing the results
it indicates that the two simulations will bring different harms to the voltage transformer. This paper presents to remove high voltage cable in reactor lowering;it can effectively reduce the excitation current.