FANG Chunhua, ZHOU Yi, JIA Boyan, et al. Study of the Characterization Method of Insulator Contamination Degree Based on the Phase Difference of LC[J]. High voltageapparatus, 2016, 52(2): 7-12.
FANG Chunhua, ZHOU Yi, JIA Boyan, et al. Study of the Characterization Method of Insulator Contamination Degree Based on the Phase Difference of LC[J]. High voltageapparatus, 2016, 52(2): 7-12. DOI: 10.13296/j.1001-1609.hva.2016.02.002.
Study of the Characterization Method of Insulator Contamination Degree Based on the Phase Difference of LC
In order to overcome the difficulties of real-time monitoring and the low accuracy of prediction technique to the pollution degree of suspension insulator in the power system operation
in this paper
large amount of artificial pollution experiments to the XP-70 insulator are done in multi-factor environmental test chamber. By changing the humidity slowly in the range of unsaturated humidity
the change law of phase difference(θ)of applied voltage and LC and the quantitative relationship between θ and ambient humidity(RH)
ESDD
NSDD are obtained.The results are as follows: θ and RHpresent a significant negative correlation
in particular
the correlation is more obvious when RH>65%
meanwhile
θ is more sensitive to pollution degree change
hence θ could be a characterization to reflect the degree of wetting and surface contamination. The ratio(k)of θ and humidity range can be used as the parameter to characterize the degree of pollution. And the contamination level of insulator surface would be calculated using the relational expression after RH
θ measured. This method can be used as an effective way for real-time monitoring of pollution degree.