WENG Lingyun, ZHANG Guangtai, LI Lei, et al. Research on the Internal Insulation Characteristic of 220 kV GIS Electronic Voltage Transformer[J]. High voltageapparatus, 2016, 52(2): 142-147.
WENG Lingyun, ZHANG Guangtai, LI Lei, et al. Research on the Internal Insulation Characteristic of 220 kV GIS Electronic Voltage Transformer[J]. High voltageapparatus, 2016, 52(2): 142-147. DOI: 10.13296/j.1001-1609.hva.2016.02.023.
Research on the Internal Insulation Characteristic of 220 kV GIS Electronic Voltage Transformer
对220 k V电子式电压互感器内部绝缘特性进行了研究。首先通过理论分析得出互感器内部电场分布和场强
采用增加屏蔽结构对场强集中处进行了优化改进
最后结合有限元仿真和实验对改进后的互感器内部绝缘进行了验证
分析及试验表明互感器的绝缘特性满足运行要求。
Abstract
Under the rapid development of smart substation technology
electronic voltage transformer used in 220 k V gas insulated switchgear(GIS) has been gradually applied in smart substation. The insulation performance of the electronic voltage transformer is a key factor for its long-term reliability and measurement accuracy. And to ensure the transformer internal insulation strength is particularly important. The paper
combining theoretical analysis
finite element and experimental methods
researches on the internal insulation property of electronic voltage transformer.Firstly
the distribution of the electric field and electric field strength is studied by theoretical analysis; Then the optimization method of added internal shield cover is given; Finally
combining finite element and experimental methods
the internal insulation of optimized transformer is verified. The results show that the internal insulation property can satisfy the needs of transformer long-term reliability.