GOU Yang, FAN Chuan, WANG Yanan, et al. Development of Resistive Impedance Divider Used for Transient Enclosure Voltage Measurement in GIS[J]. High voltageapparatus, 2016, 52(3): 34-43+49.
GOU Yang, FAN Chuan, WANG Yanan, et al. Development of Resistive Impedance Divider Used for Transient Enclosure Voltage Measurement in GIS[J]. High voltageapparatus, 2016, 52(3): 34-43+49. DOI: 10.13296/j.1001-1609.hva.2016.03.006.
Development of Resistive Impedance Divider Used for Transient Enclosure Voltage Measurement in GIS
Along with the development of ultra high voltage(UHV) transmission technology in China
transient enclosure voltage(TEV) generated in gas-insulated switchgear(GIS) may threaten the safety of staffs and secondary equipment
so accurate measurement of TEV is necessary. This paper develops a resistive impedance divider to measure the TEV in UHV GIS and the influences of structure and parameters to the square wave response of the divider are studied. The simulation and experiment result shows that
with grading sleeve installed on the high voltage side of resistor and increase of its length
the rise time of square wave response gradually decrease
but the overshoot will increase rapidly after the length of sleeve exceed a certain value. With shielding sleeve installed on the low voltage side of resistor
the rise time of square wave response increases signally due to the increase of capacitance to ground. In this paper
voltage rise time of the divider is about 3 ns
partial response time is 1.9 ns and overshoot is about 8.7%
experiments of the divider demonstrate that the electric insulating property
scale factor and square wave response of it satisfy the demand of TEV measurement in UHV GIS. This TEV measurement equipment has been used to carry out on-site TEV measurement in UHV AC test base