ZHAO Yongjin, XIE Qingfeng, ZHANG Liangxian. Optimization and Analysis on the Key Insulation Structure of 500 kV Radial Split Transformer[J]. High voltageapparatus, 2016, 52(3): 137-141+146.
The split transformer can limit the short circuit current at LV side efficiently
so this LV split type transformer is widely applied to starting-up standby transformer in power station. In order to ensure the reliability of the insulation structure in 500 k V radial split transformer
FEM is used to analyze the electric field distribution of end insulation in HV winding
lead insulation and outlets insulation of HV winding. The insulation structure optimization of key parts in transformer is done. The static ring structure of the high voltage winding is changed to composite insulation structure
and the shielding structure on the edge of the spring-loaded device corners of HV lead insulation is improved. All these measures make the main insulation structure of split transformer meet the margin requirements. The results in this paper can provide a theoretical basis for operational reliability analysis
and provide references for the insulation design of split transformer above 500 k V voltage level.