Analysis on a Fault of Grading Capacitor for 500 kV Circuit Breaker
A discharge breakdown fault of grading capacitor of 500 k V circuit breaker in a converter station
which occurred in breaker opening process
is analyzed. According to the field inspection record
the fault waveform record
the recall-checking record and the test data
the cause of the breakdown of grading capacitor
as well as the cause of the breakdown and carbonization of the insulating cylinder
is investigated. The results show that the operating overvoltage and discharge current in the process of breaker opening resulted in the breakdown fault. Some countermeasures against the logical problem in DC station control system are put forward
and some improvement approaches are suggested in order to improve the reliability of operation and maintenance of the electrical equipment.