HAN Xutao, LIU Zehui, LI Junhao. Study on the Dielectric Loss Test Methods of “Oil-Oil”Bushing Cable Outgoing Line Transformers with High Voltage Line[J]. High voltageapparatus, 2016, 52(4): 117-122.
HAN Xutao, LIU Zehui, LI Junhao. Study on the Dielectric Loss Test Methods of “Oil-Oil”Bushing Cable Outgoing Line Transformers with High Voltage Line[J]. High voltageapparatus, 2016, 52(4): 117-122. DOI: 10.13296/j.1001-1609.hva.2016.04.018.
Study on the Dielectric Loss Test Methods of “Oil-Oil”Bushing Cable Outgoing Line Transformers with High Voltage Line
The method of the dielectric loss test of transformers with "oil-oil"bushing-cable leading-out without disassembling high voltage lead is mainly studied in this paper. According to the related standards and the filed situation
dielectric loss is tested by applying voltage on the neutral point of the high voltage winding. The results are analyzed by building equivalent circuit model. It can be concluded that the measured capacitance is larger and the value of the tanδ is smaller because of there is no short-circuiting connecting between the ends of the winding
but the variation can be ignored. It is also shown that cable leads a lager capacitance and a smaller tanδ
while the PT has the opposite effects when using reverse connection method. When positive connection method is used
the impact of cable and PT is excluded
so this method is more suitable for the dielectric loss test without disassem-bling high voltage lead.