DAI Dongyun, LUO Hu, YIN Xiaogang, et al. On-line Monitoring and Fault Diagnosis Method of Vacuum Circuit Breaker with Integration Monitoring Permanent Magnetic Actuator[J]. High voltageapparatus, 2016, 52(4): 188-193+199.
DAI Dongyun, LUO Hu, YIN Xiaogang, et al. On-line Monitoring and Fault Diagnosis Method of Vacuum Circuit Breaker with Integration Monitoring Permanent Magnetic Actuator[J]. High voltageapparatus, 2016, 52(4): 188-193+199. DOI: 10.13296/j.1001-1609.hva.2016.04.030.
On-line Monitoring and Fault Diagnosis Method of Vacuum Circuit Breaker with Integration Monitoring Permanent Magnetic Actuator
In order to realize integration function for controlling and on-line monitoring of permanent magnetic actuator vacuum circuit breaker
the authors integrate the on-line monitoring function into the controller and use three means to trig recorder. According to the analysis of the recorder
it can realize failure diagnosis. For example
using the control command
coil current curve and mechanic characteristic curve presence or absence and presence sequence can be easy to discover the outburst failure.And using the envelope method it can easy to discover the outburst and gradual failure.The test result indicates the integrated method is good for the problem search and analysis and the overall performance improvement of permanent magnetic actuator vacuum circuit breaker.