Research on the Electric Field Distribution Characteristics of 12 kV Solid Epoxy Mold Insulated Switchgear Without Surface Metallization
文中对现有12 k V固体柜产品环氧浇注模块外表面无金属化处理时的电场分布特征进行了仿真研究。仿真结果表明
现有固体柜产品环氧浇注模块外表面无金属化层时
固体柜能够满足电场绝缘考核要求
但环氧浇注模块内部真空灭弧室结构及环氧模块与柜体外壳间隙距离对固体柜的电场分布影响显著。
Abstract
Solid insulation technology has been widely used in medium voltage
especially 12 kV switchgears. For the purpose of miniaturization
weather ability and safety of the solid insulated switchgear(SIS)
metallization treatment on insulation surface has attracted more attention in corresponding researches. However
a large proportion of the commonly used SISs are not treated by metallization on the outer surface of epoxy mold. In this study
the electric field distribution characteristics on the epoxy mold of the 12 kV switchgear without surface metallization are simulated. The results show that the SISs without metallization on epoxy mold surface can satisfy the requirement for electric field assessment
but the internal vacuum interrupter structure in epoxy mold and the distance between epoxy mold and cabinet shell have significant influence on a SIS electric field distribution.