Comparison Research on Leakage Magnetic Field and Short-circuit Force of Transformer Windings Under Different Models
The electric power system fault caused by transformer anti-short circuit capability’s insufficient seriously affect the safety of the power grid
so to carry out anti-short circuit capability reinforcement of transformer is necessary.At present
2-D axisymmetric partition model is widely used
as well as a small amount of 2-D bread line model in the theoretical model of transformer winding. In order to compare the simulation results of the two models
the characteristics of 2-D partition model and 2-D bread line model are introduced. And illustrated by an example of 220 k V three winding transformer
the transformer short-circuit current under different kinds of short circuit conditions are analyzed.And then the two kinds of modeling of winding’s leakage magnetic field and short-circuit electro dynamic force distribution are calculated and compared in the ANSYS. The results show that two kinds of model simulation have a certain difference but an uniformity overall distribution. So when it does not require high accuracy of leakage magnetic
2-D partition model can be used instead of bread line model in the analysis of winding leakage magnetic field.