WEI Peng, LIU Jiankun, ZHOU Qian, et al. Research on Commutation Failure of Jin-Su DC Transmission Project Caused by a Complex AC Fault[J]. High voltageapparatus, 2016, 52(5): 96-100+108.
WEI Peng, LIU Jiankun, ZHOU Qian, et al. Research on Commutation Failure of Jin-Su DC Transmission Project Caused by a Complex AC Fault[J]. High voltageapparatus, 2016, 52(5): 96-100+108. DOI: 10.13296/j.1001-1609.hva.2016.05.016.
Research on Commutation Failure of Jin-Su DC Transmission Project Caused by a Complex AC Fault
Commutation failure is an important factor on safe and stable operation of the receiving end power grid for HVDC project. A commutation failure event in Jin-Su DC transmission project caused by a complex AC failure is taken as background
the process of fault and action sequences of protection are introduced. And the reason of the commutation failure and protection action is analyzed from principle. RTDS is connected to the true-type device of UHVDC control and protection to form a closed-loop simulation platform. The commutation failure event is inversed and the simulation result is compared with the actual recorded waveform. The results show that abnormal AC voltage leads to the commutation failure.