LIU Xinhe, WU Jinlong, GUO Ningning, et al. Analysis of Submodule Capacitor Voltage Caused by DC Pole-to-pole Fault in FBMMC HVDC System[J]. High voltageapparatus, 2016, 52(5): 101-108.
LIU Xinhe, WU Jinlong, GUO Ningning, et al. Analysis of Submodule Capacitor Voltage Caused by DC Pole-to-pole Fault in FBMMC HVDC System[J]. High voltageapparatus, 2016, 52(5): 101-108. DOI: 10.13296/j.1001-1609.hva.2016.05.017.
Analysis of Submodule Capacitor Voltage Caused by DC Pole-to-pole Fault in FBMMC HVDC System
DC link faults ride through is one of the most important research objects in modular multilevel converter HVDC system. The HVDC system based on full-bridge sub-module(FBMMC HVDC)can provide counter electromotive force opposite to the current direction after the sub-modules blocked. Therefore it is an ideal topology to fast clearance the DC link faults without opening of the AC circuit breaker. This paper analyzed the sub-module capacitor voltage for FBMMC HVDC at the situation of DC pole-to-pole short circuit fault. The result shows that the module voltage will experience successively drop and uplift. This process is significance for the design of DC fault detection method
the sub module capacitance voltage tolerance