WEI Lei, GUO Jie, JIA Honggang, et al. Study on the Feasibility of Removing the Opening and Closing Resistor of Disconnecting Switch in 750 kV GIS[J]. High voltageapparatus, 2016, 52(5): 136-140+147.
WEI Lei, GUO Jie, JIA Honggang, et al. Study on the Feasibility of Removing the Opening and Closing Resistor of Disconnecting Switch in 750 kV GIS[J]. High voltageapparatus, 2016, 52(5): 136-140+147. DOI: 10.13296/j.1001-1609.hva.2016.05.023.
Study on the Feasibility of Removing the Opening and Closing Resistor of Disconnecting Switch in 750 kV GIS
With Xi’annan 750 kV GIS as the project background
the feasibility of removing the opening and closing resistor of disconnecting switch is studied. Seven modes of connection have been chosen and seven ATP-EMTP models have been built to operate every disconnecting switch in the models and the voltage of important nodes is recorded
what’s more
the frequency amplitude domain analysis against those voltage wave shapes with high amplitude is made to make sure whether it is VFTO and then it is checked by the lightning impulse withstand voltage. The results show that after removing the opening and closing resistor
when the disconnecting switches are operated
the voltage on the income casing
the circuit breaker borderupon the operated disconnecting switch
and the disconnecting switch border upon the operated disconnecting switch and connected on the same bus with it are relatively high
but they are also under the lightning impulse withstand voltage of the equipment. So a conclusion could be drawn that from the point of insulation coordination
the opening and closing resistor of disconnecting switch in 750 kV GIS could be removed.