LI Bin, YU Xin, TONG Zhihong, et al. Review and Prospect of the Organic Insulated Bus in China[J]. High voltageapparatus, 2016, 52(6): 9-17. DOI: 10.13296/j.1001-1609.hva.2016.06.002.
Review and Prospect of the Organic Insulated Bus in China
This article reviews the development of various organic insulated bus(tubular insulated bus) in China
including their advantages & shortcomings
and their contributions and problems. These problems reflect outstanding in: tubular insulated bus in the bus and the bus connector. Due to the electric field distribution is very poor
bus to ground flashover often occurs; some tubular insulated bus and switch equipment
arrester electrical interface
because of the electric field concentration
corona often occurs and further to flashover
or due to the lack of effective insulation size design
manufacture and assembly quality is not good and bus discharge to the ground
to the operation unit caused by power loss. This paper analyzes the cause of the accident
also put forward the improvement and improved suggestion. In our country
during the difficult development process of varieties of organic insulated bus
the author also sees the hope: the development prospects for a new type of capacitive compositely insulated bus. The bus is connected with the bus
the bus and other electric apparatus
and the design of multiple capacitor shields are adopted
the electric field distribution is uniform
and the insulation of the interface is reliable. In this paper
the characteristics of the material
manufacturing process and quality control and other aspects of the bus insulation reliability and control of the unique experience of partial discharge.Partial discharge is a tubular insulated bus lifeline long-term safe operation
which controls the tubular insulating bus PD characteristic
grasps the insulated tube bus to the direction of high/ultra high voltage.