YU Liangqing, WANG Hongtao, WEI Junmei, et al. Development of 1100 kV Spacer[J]. High voltageapparatus, 2016, 52(6): 29-33. DOI: 10.13296/j.1001-1609.hva.2016.06.005.
研制开发高参数、高性能的1 100 k V盆式绝缘子是保证1 100 k V特高压GIS安全可靠运行的基础。详细介绍了所研制开发的1 100 k V盆式绝缘子的设计特点;应用有限元分析计算软件对其绝缘性能和机械性能进行了详细的计算分析
计算结果表明:接地屏蔽环可以有效降低其三交区电场强度。介绍了1 100 k V盆式绝缘子的浇注工艺。该1 100 k V盆式绝缘子在产品质量检测中心顺利通过了整套型式试验
其雷电冲击耐受水平高达2 880 k V
爆破压力最低达3.15 MPa
最高达4.0 MPa
验证了其绝缘性能及机械性能的高可靠性。
Abstract
In GIS
the spacer is used for separating adjacent gas compartments
supporting conductor
and insulation. Development of a reliable 1 100 k V spacer is very important to ensure the safe service of a1 100 k V GIS. In this paper
the characters of the 1 100 k V spacer developed by NHVS are introduced
and its dielectric performance and mechanical performance are computed with a finite element analysis software. The results show that the grounding shield ring can weaken the electric field strength in the triple zone. The casting process of the spacer is also introduced. This 1 100 k V spacer has passed type test in High Voltage Apparatus Quality Test & Research Center
where its lightning pulse withstand voltage reached 2 880 k V
and its minimum and maximum burst pressure reached 3.15 MPa and 4.0 MPa
respectively
verifying its high dielectric and mechanical performances.