WANG Chaowu, GAO Xiangxiang, LI Gang, et al. Application and Simulation Computations of Current Zero Distortion for UHV Circuit-breaker Short Circuit Test[J]. High voltageapparatus, 2016, 52(6): 46-49.
WANG Chaowu, GAO Xiangxiang, LI Gang, et al. Application and Simulation Computations of Current Zero Distortion for UHV Circuit-breaker Short Circuit Test[J]. High voltageapparatus, 2016, 52(6): 46-49. DOI: 10.13296/j.1001-1609.hva.2016.06.008.
Application and Simulation Computations of Current Zero Distortion for UHV Circuit-breaker Short Circuit Test
并以1 100 k V/63 k A试验方式T100a断路器为例应用仿真模型计算了电弧电压对电流半波幅值和持续时间的衰减百分比
计算结果可以为断路器短路试验时提供理论参考。
Abstract
During the current interruption process
the arc voltage across the contacts causes the prospective short-circuit current distorted as the current approaches zero. According to the annex A of IEC 62271-101:2012
theoretical analysis the distortion current expressions with the constant arc voltage and linearly rising arc voltage respectively. Using the MATLAB/Simulink platform
established the distortion current dynamic mathematical simulation model which is respectively with constant arc voltage and linearly rising arc voltage. Furthermore
we have used the dynamic mathematical simulation model to calculate the reductions of the current amplitude and the loop duration which are caused by the arc voltage based on the test duties T100 a for 1 100 k V/63 k A circuit breaker. The results of calculation can provide theoretical reference when circuit breaker short circuit test.