The transient pressure measurement in SF6 circuit breaker is of great significance for helping its structure design
and thus to improve the breaking capability. The method of measuring the transient pressure in heavy current interruptions is using a tube to insulate the pressure probes from high temperature environment. But the tube will cause high frequency oscillation in measurement results
and the influence cannot be neglected. Investigation is performed on the interference of tube structure on transient pressure measurement under heavy current interruptions. Tests on the dynamic performance of different tube structures are conducted based on shock tube facility. Several methods satisfying the measuring requirements for restraining interference are found in this paper. No-load tests and load tests are conducted with a 252 k V SF6 circuit breaker
the results prove the pressure measurement method established in this paper is effective for measuring the pressure variation in the nozzle.