Electrical Erosion Experiment and State Diagnosis on Arcing Contact of SF6 Circuit Breaker
文中提出了一种利用动静触头之间动态电阻曲线诊断弧触头状态的方法。试验通过断路器合成试验回路电流源部分对某试品断路器进行了从开断额定短路电流(有效值40 k A)零次到额定次数(22次)的烧蚀老化试验
每次烧蚀后测量其弧触头动态电阻曲线
并将与零烧损状态的曲线之间的相关系数作为弧触头烧损状态诊断的特征参数
从测试结果中发现在断路器第15次开断之后相关系数开始出现明显的变化
该现象表明弧触头寿命已经接近工作极限。试验结果证明
动态电阻曲线能够很好地反映出弧触头的烧损情况
是一种有效的SF6断路器弧触头状态诊断方法。
Abstract
As traditional type tests could not detect the state of arcing contact of an SF6 circuit breaker
this paper proposes a method to diagnose the state of the arcing contact based on the dynamic contact resistance curve between the moving and fixed contacts. The current source of synthetic test circuits is used to conduct electrical erosion experiment on the tested circuit breaker
where the rated short circuit current(40 k A RMS) is cut off from zero to 22 times. The dynamic contact resistance curve is measured after each electrical erosion experiment
and the correlation coefficient between the initial and measured curves is taken as the characteristic parameter for diagnosing the state of arcing contact. Obvious change is found on the correlation coefficient after cutting off the current for 15 times. This phenomenon illustrates the service limit of the arcing contact. Experimental results show that the dynamic contact resistance curve can perfectly reflect erosion status of the arcing contact
and it is an effective way to state diagnosis of the arcing contact.