Improvement of the Loop Resistance Measurement for 1000 kV UHV Circuit Breaker
UHV maintenance encounters the difficulties in technology
examples and experience. Especially
the measurement reliability of circuit breaker loop resistance directly relates to safe operation of UHV equipment. In this study
conventional single-phase DC voltage drop method
the improved three-phase DC voltage drop method
and the measurement without removing the headband ground were applied to the first maintenance overhaul of1000 kV UHV equipment in Lian Tang Power Station. Two kinds of 1 000 kV circuit breakers were sampled and tested by two instruments
respectively
and the comparison between the standard and delivery values indicates that the three-phase DC voltage drop method can conveniently and reliably judge whether the loop resistance value of a circuit breaker meets standard or not
while the single-phase DC voltage drop method can be used for accurately quantitative analysis.