LI Suichao, ZHAO Yu, LI Sujie, et al. Field Calibration Technology of 100 kA Large Current Transformers[J]. High voltageapparatus, 2016, 52(7): 161-167.
LI Suichao, ZHAO Yu, LI Sujie, et al. Field Calibration Technology of 100 kA Large Current Transformers[J]. High voltageapparatus, 2016, 52(7): 161-167. DOI: 10.13296/j.1001-1609.hva.2016.07.025.
Field Calibration Technology of 100 kA Large Current Transformers
In order to solve the 100 kA current transformer error calibration and quantity value transfer and traceability problem
the author introduces the a utilization of ampere measuring principle of large current transformer load excitation current and small school method to determine the 100 kA current transformer error
we begin by measuring a large current transformer secondary winding DC resistance and secondary load excitation current error
then measure the large current transformer basic error in the small current
finally
calculate the linear error turns ratio
and estimate the 100 kA large current transformer actual error
well solve the problem of the value of current difficulties in the field of large current transformers
and through a large number of experimental data proved the feasibility and correctness of the method. The results shows that the method is completely correct