CAI Feng, JIANG Xiubo, CAI Jinding. Extended Debye Equivalent Circuit Parameter Identification Based on Polarization Current[J]. High voltageapparatus, 2016, 52(8): 64-70.
CAI Feng, JIANG Xiubo, CAI Jinding. Extended Debye Equivalent Circuit Parameter Identification Based on Polarization Current[J]. High voltageapparatus, 2016, 52(8): 64-70. DOI: 10.13296/j.1001-1609.hva.2016.08.011.
Extended Debye Equivalent Circuit Parameter Identification Based on Polarization Current
Dielectric response characteristics of transformer oil-paper insulation system can be described using extended equivalent circuit of the Debye model. Study on extended Debye model equivalent circuit parameter identification method of oil-paper insulation system is of great significance. This paper proposes a method using polarization current curve to identify extended Debye equivalent circuit parameters of oil-paper insulation transformer. Because the terminal of polarization current curve depends on the large time constant exponential
so firstly
it can take the points at the end of the curve to calculate estimated values of the parameters
to modify the calculation based on estimated values to get accurate values
then check the calculation to obtain more accurate values. One branch respectively
all polarization branch parameters can be obtained. Using this method
the equivalent circuit parameters of several transformers are identified. The calculated equivalent circuit parameters are accurate and polarization current curves fitting good