Research on Resonance Overvoltage Caused by Loop Closing Operation in Distribution Network with Neutral Grounding Through Arc Suppress Coil
In the loop closing operation of distribution network with neutral grounding through arc suppression coil
the circuit structure changes will cause the mismatch of the parameters of zero sequence circuit
triggering the linear resonance overvoltage
this paper mainly concentrates on this problem and is to find some solutions. The paper analyzes the zero sequence overvoltage in the loop closing operation of distribution network with neutral grounding through arc suppression coil. Additionally
by using ATP software
a distribution network is taken as an example to calculate the resonance overvoltage in the loop closing operation and related influencing factors are discussed. The result shows that the voltage of neutral point may be magnified
and the amplitude is influenced by damping of the system
off tuning degree of the arc suppression coil and asymmetry degree of the line. According to the theoretical analysis and simulation results
several measures to reduce the neutral voltage offset are proposed. The research in this paper provides an important reference for safe operation of distribution network and scientific proper selection of compensation scheme.