Analysis on Overvoltages Caused by Vacuum Circuit Breakers Switching off Shunt Reactors and Its Suppression Measures Based on ATP-EMTP
When using vacuum circuit breaker to switch shunt reactors
the current chopping
overvoltage with repeatedly renewed and other hazards will come along. Those hazards do destabilize power system operation. Based on ATP-EMTP
this paper firstly simulates the actual operation of substation
and it is found that in the bus side
load side and a reactor side there are serious phase-to-ground overvoltage and phase-to-phase overvoltage. Then combining the type and severity of the overvoltage
different protection devices are used to simulate the protecting effectiveness. Finally
according to the actual operation of substation
overvoltage conditions after applying different protection schemes are simulated and computed. Research results indicated that
the overvoltage induced by switching off shunt reactors can reach two times higher than normal overvoltage induced by single phase cut-off;overvoltage between phase to phase is obviously higher than that between phase to ground; mounting two-way RC overvoltage protection on the load side of the draw and the reactor side should be the best approach to guarantee the security and stability of the substation
which is able to lower the overvoltage by 50% to 69%.