Optimized Design for HVDC Voltage Divider Internal Temperature Field
DC voltage divider is indispensable for DC power transmission system. Owing to its structure and principle
DC voltage divider has a great temperature gradient inside
which affect its error performance and increase the flashover probability of the hollow insulator. For the heat problem
this paper improves the structure of the ±1 100 kV DC voltage transformer’s internal temperature field
while improving the cooling structure of the top
this design can lower its temperature gradient. Finally
Ansys Fluent is used to simulation the new design for the analysis of the temperature distribution and heat flux field
the results show that
in the case of the primary current is 2 m A and the heat flow is 2.2 k W
the new DC voltage divider internal temperature decreases significantly compared to the conventional structure at an ambient temperature of 27 ℃
the temperature difference can reach 20 K. The cooling structure of the top increases the gas flow inside the divider and improves the efficiency of the heat dissipation
this optimized design can meet the cooling requirement.