Electrodynamic Force Analysis and Design Improvement of 12 kV Withdrawable Circuit Breaker
To solve the tulip contact erosion problem of a 12 kV withdrawable circuit breaker
the electrodynamic force on the circuit breaker with short circuit current was analyzed
a structural mechanics analysis of the circuit breaker under the electrodynamic force was conducted by means of using finite element analysis software
and the causes of the erosion were obtained. Subsequently
the design was improved. Type test of the circuit breaker and the measured deformation of the contact under real electrodynamic force verify the correctness of the above analysis and design optimization. In addition
the effects of electrodynamic force on the 12 kV withdrawable circuit breaker in different test conditions were achieved.