ZHENG Yongwu, HUANG Xiuzuo. Simulation Study on the Response Characteristic of Tian-Guang DC Transmission System of Low DC Voltage Measurements at the Inverter Side[J]. High voltageapparatus, 2016, 52(9): 148-152.
ZHENG Yongwu, HUANG Xiuzuo. Simulation Study on the Response Characteristic of Tian-Guang DC Transmission System of Low DC Voltage Measurements at the Inverter Side[J]. High voltageapparatus, 2016, 52(9): 148-152. DOI: 10.13296/j.1001-1609.hva.2016.09.026.
Simulation Study on the Response Characteristic of Tian-Guang DC Transmission System of Low DC Voltage Measurements at the Inverter Side
Several abnormal voltage elevation events of Tian-Guang DC transmission system happened recently resulting from the low DC voltage measurement at its inverter side. In this paper
the cause of the abnormal DC voltage elevation is analyzed based on the control strategy of Tian-Guang DC transmission system. A large number of RTDS simulation tests are conducted to investigate the over-voltage level and the response characteristics of the control and protection systems of the DC transmission system when DC voltage measurement at the inverter side is low in the cases of different grade of low DC voltage measurement fault
power level and operating mode. Simulation results show that low DC voltage measurement at the inverter side will result in overvoltage on DC system
the DC system will exhibit different control and protection performances at different fault levels
power levels and operating modes
and DC overvoltage level can be reduced in the case of high power mode and voltage-down operation mode.