Numerical Solution of the Surface Electric Field of the Fittings in DC Field of ± 500 kV HVDC Converter Station
The accurate calculation of the surface electric field on equipment fittings in HVDC converter station will help to make corona control and anti-corona design. For HVDC converter station field is of complicated equipment
large computational domain
high precision of special fittings local surface field computing
a±500 kV HVDC converter station field is taken for the study. Based on field numerical calculation method
3D finite element simulation model of the entire DC field equipment is built for field computing
and the calculation of various parts of the potential and the electric field distribution is obtained. Through the results of the full model analysis
the parts which need to be focused on are more accurate solved by the use of sub-models
and a more accurate value of the electric field strength is gotten. Finally
based on the Peek formula
the corona control margin of safety assessment for all fittings in DC field is made. Results show that DC field with each fittings surface electric field control of the maximum field strength in line with the requirements
the results can provide reference to the design and planning of extra-and ultra-high voltage direct current converter station.