Study of Comprehensive Suppression Method for Distribution Network Ferromagnetic Resonance
Ferromagnetic resonance seriously influences the security and stability of 10 kV power systems. When studying the suppression method of distribution network ferromagnetic resonance
the researchers usually con sider the individual method
and comprehensive suppression method has not been widely mentioned. This paper selected the 10 kV system of a 110 kV substation which ferromagnetic resonance has happened as analysis object
simulation models of distribution network ferromagnetic resonance are built based on electromagnetic transient analysis software ATP-EMTP. Three kinds of suppression measures are considered
which are the harmonic eliminator
change the excitation characteristics and damping resistance
the suppression effects of single measure and different measures combination are analyzed respectively. By comparison excellent result is obtained by use suppression methods in combination. A new idea is provided in this paper for governing ferromagnetic resonance.