Analysis of the Energy Transport Processes in DC Air and SF6 Nozzle Arcs
the insulation and interruption capability of air has been extensively investigated. Research has also recently been done to use air as a dilution gas of Fluoroketone for SF
6
free interruption in medium voltage switchgear. Much evidence has shown that air gas-blast circuit breakers have far inferior interruption capability than SF
6
breakers. However
no clear explanation has so far been given regarding why an air switching arc has much larger time constant than an SF
6
arc
and thus exhibiting far inferio
r interruption capability than the latter. Based on reliable experimental measurements
the present work first calibrated the turbulence parameter in a two-dimensional axisymmetrical turbulent arc model which was then used for computational investigation of the air arc behaviour and analysis of the dominant energy transport processes.Through comparative study
it has been found that
for air nozzle arc at low current
the radial and axial cooling mechanisms play almost equal roles
while for SF
6
arc the radial cooling mechanism is dominant. The difference in cooling mechanisms for air and SF
6
arcs is directly related to the difference in radial temperature profiles which is controlled by the material property
ρCp
through turbulence enhanced thermal conduction. The present work therefore provides clear direction on the explanation of the differing interruption performance of different SF
6
replacement gases under transient discharge conditions.