CHEN Huili, XU Jianyuan, LI Luwei, et al. Experimental Study on Breakdown Characteristics of SF6/N2 Mixtures in Non-uniform Electric Field[J]. High voltageapparatus, 2016, 52(12): 110-115.
CHEN Huili, XU Jianyuan, LI Luwei, et al. Experimental Study on Breakdown Characteristics of SF6/N2 Mixtures in Non-uniform Electric Field[J]. High voltageapparatus, 2016, 52(12): 110-115. DOI: 10.13296/j.1001-1609.hva.2016.12.017.
Experimental Study on Breakdown Characteristics of SF6/N2 Mixtures in Non-uniform Electric Field
mixtures in non-uniform electric field are studied. The positive and negative breakdown voltages are measured in the rod-plate electrode at different gap lengths
mixing ratios and pressures. The effects of polarity for different electric field distribution and gas pressure is analysed. It is shown that with a pressure of 0.1 MPa
the breakdown voltage in N
2
increases with the gap
length and the negative breakdown voltage is higher than the positive breakdown voltage. The former is 1.71 times of the latter for a gap length of 12 mm. opposite to N
2
the positive breakdown voltage of SF
6
gas is higher than its negative breakdown voltage. With a gap length of 4 mm
when the gas pressure increases the negative breakdown voltage of SF
6
increases while the positive breakdown voltage appears approaches saturation before it declines. When the pressure is 0.4 MPa
the positive breakdown voltage of 20%SF
6
/80%N
2
gas mixtures is 91.3% of that of 0.35 MPa pressure.The negative breakdown voltage is higher than the positive one when the SF