CHENG Wei, SU Zhenxi, MA Fengxiang, et al. Research on Leakage Detection Technology for Electrical Equipment Insulated by SF6 Mixtures[J]. High voltageapparatus, 2016, 52(12): 146-150.
CHENG Wei, SU Zhenxi, MA Fengxiang, et al. Research on Leakage Detection Technology for Electrical Equipment Insulated by SF6 Mixtures[J]. High voltageapparatus, 2016, 52(12): 146-150. DOI: 10.13296/j.1001-1609.hva.2016.12.023.
Research on Leakage Detection Technology for Electrical Equipment Insulated by SF6 Mixtures
gas is regarded as one of the six greenhouse gases in Kyoto Protocol. In order to reduce the amount of SF
6
usage
it has been shown to be feasible to use SF
6
/N
2
and SF
6
/CF
4
mixtures as SF
6
alternatives and the mixtures have been used in some of the electrical equipment both domestically and abroad. There has been very little research on the detection technology of SF
6
mixtures
and weather the det
ection technology of SF
6
gas is applicable to SF
6
mixtures is an issue that needs to be addressed. In this paper
we make SF
6
/N
2
and SF
6
/CF
4
mixtures as experimental subjects
simulate the leakage situations of SF
6
mixtures with different mixing ratios at different distance and under different wind speed. Infrared camera is used to detect gas leakage and to obtain the detection limit of the instrument
thus defining the optimum detecting conditions. It has been shown that the leakage detection technology for SF
6
gas can be used to detect SF
6
mixture leakage
which provides sensible guidance for the on-site detection of SF