Deformation State Analysis of High-speed Switch Type Variable Impedance Energy-saving Transformer Winding
The short-circuit impulse produced by power transformer short-circuit fault
will cause the transformer windings deformation. Therefore
it is significant to take effective measures for the purpose of limiting short-cir-cuit current to a reasonable and low level. In this paper
based on the magnetic-mechanics coupling field
the threewinding transformer of 110 kV voltage levels of windings deformation is analyzed when the threephase short-circuit fault occurs at the location of medium-voltage winding. The variable impedance energysaving trans-former
which is composed of the main body of the transformer and the current-limiting reactor
can limit fault current when the system of short-circuit fault occurs. The dynamic deformation of the body of transformer and current-limiting reactor are analyzed
containing the stress and displacement after short-circuit fault occurs.Com-pared with the conventional transformer
the maximum of windings deformation and stress of variable impedance transformer is smaller. The research results provide reference for the evaluation of variable impedance transformer winding deformation.